6. Mounting
Power down the equipment
Mount the module on standard rail (TH35 per IEC 60715 in
junction boxes and/or on distribution panels).
Installation
Electric installation and device termination shall be done by qua-
lified persons only, by respecting all applicable
specifications and regulations.
Plug in the terminal block for bus connection
43
5 mm
5 6
The module can be aligned without interspace. Use the jumper
plug to connect bus and supply voltage when the modules are
mounted in series.
The maximum quantity of modules connected in line is limited
to 15 or to a maximum power consumption of 2 Amps (AC or
DC) per connection to the power supply. For any similar block
of additional modules a separate connection to the power
supply is mandatory.
Connect the cable for bus supply
Mounting in series
7. Network adress and Bit rate setting
Configuration Switches
Hexadecimal Switches x10, x1 define the Network Address
(00 - F9; e.g. F9h = 15x16+9 = 249d) and Baud rate (FA – FF).
• Turn Switch x10 to E (Device is temporaryly configured as Slave)
• Turn Switch x1 to A – F to select Baud rate
• Turn Switch x10 to F, wait 1 second
• Red and green LEDs are blinking when Baud rate ist stored in
EEPROM
• Turn Switch x10 to select Network Address
• Turn Switch x1 to select Network Address
MS/TP Master if using Network Address 0x00 … Max_Master,
MS/TP Slave if using Network Address Max_Master + 1 … 0xF9.
Factory setting: 9600 Bit/s
Adress switch x10 F F F F F F
Adress switch x1 A B C D E F
Bit rate (Bit/s) 9600 19200 38400 57600 76800 115200
8. Software Description
Device Object
Property Remark / Value RW
Object_Identifier device, default instance: 421000 + Network-Address RW-E
Object_Name
max. 63 Bytes,
default “BMT-AO4_” + Network-Address (Hexadecimal)
RW-E
Object_Type DEVICE (8) R
System_Status OPERATIONAL (0) R
Vendor_Name “BTR Netcom GmbH” R
Vendor_Identifier 421 R
Model_Name “BMT-AO4” R
Description max. 127 Bytes, default “” RW-E
Location max. 63 Bytes, default “” RW-E
Firmware_Revision “1.2” R
Application_Software_Version “1.0” R
Protocol_Version 1 R
Protocol_Revision 12 R
Protocol_Services_Supported
read-property, write-property, subscribe-cov, who-has, who-is, device-communication-
control, reinitialize-device
R
Protocol_Object_Types_Supported DEVICE, ANALOG_OUTPUT, ANALOG_VALUE R
Object_List [6] device, analog-output 1…4, analog-value 1 R
Max_APDU_Length_Accepted 480 R
Segmentation_Supported NO_SEGMENTATION (3) R
APDU_Timeout 10000 R
Number_Of_APDU_Retries 3 R
Device_Address_Binding - R
Database_Revision 0 R
Max_Master 0…127, default 127 RW-E
Max_Info_Frames 1…255, default 1 RW-E
Active_COV_Subscriptions
max. 6 Subscriptions, for analog-output 1…4,
Confirmed / Unconfirmed, Lifetime = 0…65535 sec.
R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Analog Output Object 1…4
Property Remark / Value RW
Object_Identifier analog-output, instance 1 … 4 R
Object_Type ANALOG_OUTPUT (1) R
Object_Name max. 42 Bytes, default “Output 1” … “Output 4” RW-E
Description max. 84 Bytes, default “” RW-E
Present_Value 0.0 … 102.4 (0V … 10.24V) RW
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0 / 1
R
Event_State NORMAL (0) R
Out_Of_Service FALSE (0) / TRUE (1) RW
Units Percent (98) R
Priority_Array [16] NULL / 0.0 … 102.4 (0V … 10.24V) R
Relinquish_Default 0.0 … 102.4 (0V … 10.24V) RW-E
COV_Increment
Minimum change of Present_Value for COV notification,
default 1.0
RW-E
Notification_Class
Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast
RW-E
Resolution 0.00625 (0.625 mV) -
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash