Binary Output Object 1…4
Property Remark / Value RW
Object_Identifier binary-output, instance 1 … 4 R
Object_Type BINARY_OUTPUT (4) R
Object_Name max. 42 Bytes, default “Relay 1” … “Relay 4” RW-E
Description max. 84 Bytes, default “” RW-E
Present_Value NULL (write only) / INACTIVE (0) / ACTIVE (1) RW
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0 = Switch A (Auto)
1 = Switch 0 (Off) or 1 (On)
OUT_OF_SERVICE: 0 / 1
R
Event_State NORMAL (0) R
Out_Of_Service FALSE (0) / TRUE (1) RW
Polarity NORMAL (0) / REVERSE (1) RW-E
Priority_Array [16] NULL / INACTIVE (0) / ACTIVE (1) R
Relinquish_Default INACTIVE (0) R
Inactive_Text max. 20 Bytes, default “Off” RW-E
Active_Text max. 20 Bytes, default “On” RW-E
Notification_Class
Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast
RW-E
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Function Table for Binary Output
Out_Of_Service
Polarity Switch Priority_Array Present_Value Binary Output OVER RIDDEN
OUT_OF_SERVICE
0 0 A NULL / 0 / 1 0 / 0 / 1 0 / 0 / 1 0 0
0 0
0
1
NULL / 0 / 1
NULL / 0 / 1
0
1
0
1
1 0
0 1 A NULL / 0 / 1 0 / 0 / 1 1 / 1 / 0 0 0
0 1
0
1
NULL / 0 / 1
NULL / 0 / 1
1
0
0
1
1 0
1 0 A NULL / 0 / 1 0 / 0 / 1 0 0 1
1 0
0
1
NULL / 0 / 1
NULL / 0 / 1
0 / 0 / 1
0 / 0 / 1
0
1
0 1
1 1 A NULL / 0 / 1 0 / 0 / 1 1 0 1
1 1
0
1
NULL / 0 / 1
NULL / 0 / 1
0 / 0 / 1
0 / 0 / 1
0
1
0 1
Fortsetzung Beschreibung der Software
Analog Value Object 1
Property Remark / Value RW
Object_Identifier analog-value, instance 1 R
Object_Type ANALOG_VALUE (2) R
Object_Name max. 42 Bytes, default “Watchdog Time” RW-E
Description max. 84 Bytes, default “” RW-E
Present_Value
Time Constant of Watchdog Timer,
0: Watchdog is inactive, Maximum: 655.34 seconds
RW-E
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
R
Event_State NORMAL (0) R
Out_Of_Service FALSE (0) R
Units seconds (73) R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Der Watchdog Timer setzt Present_Value von allen Ausgangsobjekten zurück auf Relinquish_Default, wenn die BACnet Kommunikation
dauerhaft ausfällt. Der Timer wird neu gestartet, wenn eine BACnet Nachricht mit einer APDU empfangen wird.
Wenn der Timer ausläuft, werden die Prioritätsfelder alle Ausgangsobjekte komplett auf NULL gesetzt.