accommodate this signal generation while maintaining
compatibility with coaxial and fiber optic signals.
Timers
A simple crystal oscillator and divider are used to develop the
unlatch delay time and reconfiguration timers. Although not
critical, the unlatch delay timer is more repeatable from a
crystal oscillator. However, the reconfiguration timer is more
critical. The reconfiguration timer does not sense a
reconfiguration on the network, it only predicts that a
reconfiguration will occur. This is accomplished by noting that
no data has occurred for 82 µs (at standard timeouts). Once this
timer is exceeded, the yellow RECON LED is lit for about
950 ms. If the hub is operated on a network with extended
ARCNET timeouts, jumpers must be set on the timing module
to extend the reconfiguration timer to match the network
timeouts. There are a total of four jumper settings
corresponding to the four possible timeouts.
Watchdog Timer
If no hub activity is sensed after a predetermined time, a
watchdog timer will automatically reset the MOD HUB timing
module. This is to ensure that the hub reestablishes
communication after a significant electrostatic or
electromagnetic phenomenon without requiring any human
intervention.
TD401600-0MO
23