TD040300-0MF
30
6.1.3.3 System Configuration
Four tabs exist on the configuration screen. Select System if it is not already highlighted.
System Name Give your system any name you wish.
IP Address Changing the default value of 192.168.92.68 is recommended.
Subnet Mask The default value of 255.255.255.0 is adequate for most users.
Gateway Address If your Ethernet LAN has a gateway (router) enter its address here.
Main Unit Name Give your Master module any name you wish.
Expansion Units Choose from the default of 0 to as many as 3 units. This value will
set the number of tabs that you see atop the main screen.
NOTE: Whether you are configuring System, BACnet,
Modbus or Virtual values, clicking “UPDATE” will save
your values to internal memory, but you must reboot
the Master module by cycling power before the new
values will apply!
After the Master has been given its initial configuration, it will be ready for use in the full
original Ethernet network. The temporary Ethernet network constructed in Figure 13
should be dismantled and the PC re-configured to restore its original IP address.
Figure 17 — Configuring System in the Master Module